Also for Siemens SIMATIC NET: Operating Instructions Manual (29 pages), Operating Instructions Manual (50 pages), Operating Instructions Manual (28 pages), Assembly Instructions Manual (6 pages), Product Information (6 pages), Installation Manual (40 pages), Installation Manual (50 pages), Reference Manual (14 pages), Installation Manual (34 pages), Installation Manual (48 pages), Operating Instructions Manual (32 pages)

Siemens SIMATIC NET Installation Manual
a
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
Note
The RUGGEDCOM RMC30 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Fast Transient
Dielectric Strength
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
RUGGEDCOM RMC30
Installation Manual, 04/2021, C79000-G8976-1008-10
Test
HV Impulse
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
6.2 EMC and Environmental Type Tests
Description
Signal Ports
DC Power
Ports
AC Power
Ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Description
Test Ad
Test Bd
Test Db
Certification
Test Levels
5 kV  (Fail-Safe
Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1MHz
2.5 kV common, 1 kV
differential mode @ 1MHz
2.5 kV common, 1 kV
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV
1.5 kV
2 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (non-
condensing), 55 °C
(131 °F), 6 cycles
Severity
Levels
 
 
 
 
 
 
29