Installation and operation
3.2 Operation
• Check in the "Localization Configuration" client whether the "CCP" and "Data Sending Period"
parameters are configured the same on both interfaces (green frame, blue frame).
• Restart the gateway via the "Reset" button (red frame).
Variant 2:
The functions of the radio interfaces are retained, but the radio parameters are changed to
match the transponders.
Advantages: Can be done via mass configuration for all devices at the same time.
Disadvantages: Various radio interface conversions, non-ideal antenna configuration in
gateway.
The parameters can be configured in the Locating Manger by a trained commissioning
engineer.
• In the "Localization configuration" client, change UWB channel 5 to UWB channel 2 at "TDoA
timesync (channel IF2)".
• Then change UWB channel 2 to UWB channel 5 in "Localization (channel IF4)".
• Adapt PRF and preamble on both interfaces so that interface 4 (IF4) is configured identically
to the transponder.
• Red frame: Set the UWB channel for interface 2 (IF2) to channel 2 and then click the "Set"
button.