Also for Siemens Simatic S7-1500: Manual (40 pages), Manual (47 pages), Manual (24 pages), Manual (34 pages), User Manual (45 pages), Manual (27 pages), Configuration Manual (20 pages), Manual (47 pages), Manual (43 pages), Manual (48 pages), Manual (26 pages), Manual (28 pages), Manual (50 pages), Manual (34 pages), User Manual (44 pages), Manual (50 pages), Manual (30 pages), Manual (41 pages), Manual (50 pages), Manual (40 pages), Safety Programming Manualline (48 pages), Communication Instruction Manual (36 pages), Manual (40 pages), Manual (25 pages), Manual (42 pages), Application Description (50 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (41 pages), Manual (46 pages), Manual (38 pages), Manual (35 pages), Manual (39 pages), Manual (28 pages), Manual (35 pages), Equipment Manual (35 pages), Manual (50 pages), Equipment Manual (32 pages), Equipment Manual (38 pages), Manual (29 pages), Equipment Manual (38 pages), Manual (34 pages), Manual (36 pages), Equipment Manual (50 pages), Manual (45 pages)

Siemens Simatic S7-1500 Manual
Address space for configuration as 4 x 8-channel DQ 32x24VDC/0.5A HF S QI
For the configuration as a 4 x 8-channel module, the channels of the module are divided into
multiple submodules. The submodules can be assigned to different IO controllers when the
module is used in a shared device.
The number of IO controllers depends on the interface module used. Please observe the
information in the manual for the particular interface module.
Contrary to the 1 x 32-channel module configuration, each of the four submodules has a
freely assignable start address. The addresses for the respective value status of a
submodule can also be assigned by the user.
Figure 4-2
Address space for configuration as 1 x 32-channel DQ 32x24VDC/0.5A HF MSO
For the configuration as a 1 x 32-channel module (module-internal Shared Output, MSO),
channels 0 to 31 of the module are copied to multiple submodules. Channels 0 to 31 are
then available with identical values in various submodules. These submodules can be
assigned to up to four IO controllers when the module is used in a shared device:
● The IO controller to which submodule 1 is assigned has write access to outputs 0 to 31.
● The IO controllers to which submodule 2, 3, or 4 is assigned have read access to outputs
0 to 31.
The number of IO controllers depends on the interface module used. Observe the
information in the manual for the particular interface module.
Digital output module DQ 32x24VDC/0.5A HF (6ES7522-1BL01-0AB0)
Manual, 09/2016, A5E35683508-AB
Address space for configuration as 4 x 8-channel DQ 32x24VDC/0.5A HF S QI with
value status
Parameters/address space
4.3 Address space