Also for Siemens Simatic S7-1500: Manual (40 pages), Manual (37 pages), Manual (47 pages), Manual (24 pages), Manual (34 pages), User Manual (45 pages), Manual (27 pages), Configuration Manual (20 pages), Manual (47 pages), Manual (43 pages), Manual (26 pages), Manual (28 pages), Manual (50 pages), Manual (34 pages), User Manual (44 pages), Manual (50 pages), Manual (30 pages), Manual (41 pages), Manual (50 pages), Manual (40 pages), Safety Programming Manualline (48 pages), Communication Instruction Manual (36 pages), Manual (40 pages), Manual (25 pages), Manual (42 pages), Application Description (50 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (41 pages), Manual (46 pages), Manual (38 pages), Manual (35 pages), Manual (39 pages), Manual (28 pages), Manual (35 pages), Equipment Manual (35 pages), Manual (50 pages), Equipment Manual (32 pages), Equipment Manual (38 pages), Manual (29 pages), Equipment Manual (38 pages), Manual (34 pages), Manual (36 pages), Equipment Manual (50 pages), Manual (45 pages)

Siemens Simatic S7-1500 Manual
Connecting up
Note
PROFINET interface X3 with a transmission rate of 1000 Mbps
The PROFINET interface X3 supports a maximum transmission rate of 1000 Mbps.
Requirements:
• Devices on the PROFINET segment must support the 1000 Mbps transmission rate.
• The network infrastructure (network cables and outlets) must be category CAT 5e or
higher.
• The "Transmission rate" parameter in the properties of the port (X3) must be set as
follows in STEP 7:
– The "Autonegotiation" check box is selected
– "Automatic" is selected in the drop-down list
PROFIBUS interface X4
The table below shows the terminal assignment of the PROFIBUS interface. The assignment
corresponds to the standard assignment of an RS485 interface.
Table 3- 1
Note
Supply of I/O devices
The CPU 1518-4 PN/DP ODK does not provide a 24 V DC power supply on the PROFIBUS
interface. I/O devices (for example, PC adapter USB 6ES7972-0CB20-0XA0) are only
operational on the interface in conjunction with a plug-in power supply set for external power
supply.
The innovative successor product, PC adapter USB A2, receives the required power supply
via the USB port. This means it does not need a 24 V DC supply voltage and can be
operated without a plug-in power supply set for external power supply.
30
PROFIBUS interface terminal assignment
View
1
2
3
4
5
6
7
8
9
Signal name
-
-
-
-
RxD/TxD-P
Data line B
RTS
Request To Send
M5V2
Data reference potential (from station)
P5V2
Supply plus (from station)
-
-
RxD/TxD-N
Data line A
-
-
CPU 1518-4 PN/DP ODK (6ES7518-4AP00-3AB0)
Designation
Manual, 09/2016, A5E35681108-AA