Also for Siemens Simatic S7-1500: Manual (40 pages), Manual (37 pages), Manual (47 pages), Manual (24 pages), Manual (34 pages), User Manual (45 pages), Manual (27 pages), Configuration Manual (20 pages), Manual (47 pages), Manual (43 pages), Manual (48 pages), Manual (26 pages), Manual (28 pages), Manual (34 pages), User Manual (44 pages), Manual (50 pages), Manual (30 pages), Manual (41 pages), Manual (50 pages), Manual (40 pages), Safety Programming Manualline (48 pages), Communication Instruction Manual (36 pages), Manual (40 pages), Manual (25 pages), Manual (42 pages), Application Description (50 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (41 pages), Manual (46 pages), Manual (38 pages), Manual (35 pages), Manual (39 pages), Manual (28 pages), Manual (35 pages), Equipment Manual (35 pages), Manual (50 pages), Equipment Manual (32 pages), Equipment Manual (38 pages), Manual (29 pages), Equipment Manual (38 pages), Manual (34 pages), Manual (36 pages), Equipment Manual (50 pages), Manual (45 pages)

Siemens Simatic S7-1500 Manual
Resistor circuitry of the encoders
To detect a wire break, it is necessary that enough quiescent current is flowing even when
the encoder contacts are open. Connect a resistor of 25 kΩ to 45 kΩ with 0.25 W to the
encoder contacts for this reason.
Figure 3-2
Tip: Using the potential jumpers
If you want to supply both load groups with the same potential (non-isolated), use the
potential jumpers supplied with the front connector. This helps you to avoid having to
terminate two wires to one terminal.
Proceed as follows:
1. Connect the 24 V DC supply voltage to terminals 19 and 20.
2. Insert the potential jumpers between terminals 19 and 39 (xL+) and between terminals 20
and 40 (xM).
3. Use the terminals 39 and 40 to distribute the potential to the next module
Figure 3-3
Note
Ensure that the maximum current load of 8 A per potential jumper is not exceeded.
DI 32x24VDC HF digital input module (6ES7521-1BL00-0AB0)
Manual, 09/2016, A5E03485935-AF
Resistor circuitry of the encoders
Using the potential jumpers
Wiring
15