Also for Siemens Simatic S7-1500: Manual (40 pages), Manual (37 pages), Manual (47 pages), Manual (24 pages), Manual (34 pages), User Manual (45 pages), Manual (27 pages), Configuration Manual (20 pages), Manual (47 pages), Manual (43 pages), Manual (48 pages), Manual (26 pages), Manual (28 pages), Manual (50 pages), Manual (34 pages), Manual (50 pages), Manual (30 pages), Manual (41 pages), Manual (50 pages), Manual (40 pages), Safety Programming Manualline (48 pages), Communication Instruction Manual (36 pages), Manual (40 pages), Manual (25 pages), Manual (42 pages), Application Description (50 pages), Manual (28 pages), Manual (33 pages), Manual (49 pages), Manual (36 pages), Manual (41 pages), Manual (46 pages), Manual (38 pages), Manual (35 pages), Manual (39 pages), Manual (28 pages), Manual (35 pages), Equipment Manual (35 pages), Manual (50 pages), Equipment Manual (32 pages), Equipment Manual (38 pages), Manual (29 pages), Equipment Manual (38 pages), Manual (34 pages), Manual (36 pages), Equipment Manual (50 pages), Manual (45 pages)

Siemens Simatic S7-1500 User Manual
Parameters/address space

4.3 Address space

4.3
Address space
The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the
outputs/inputs.
Configuration options of DQ 16x24VDC/0.5A HF
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 2
Configuration options
Configuration
1 x 16-channel without value status
1 x 16-channel with value status
2 x 8-channel without value status
2 x 8-channel with value status
1 x 16-channel with value status for
module-internal Shared Output with up to
4 submodules
Note
Substitute value behavior in shared device operation with the following configuration (V1.0
only):
• 2 x 8-channel with / without value status
If the system is in shared device mode and one of the IO controllers involved goes into
STOP or fails due to a communication failure, for example, all submodules of the output
module perform the configured substitute value reaction (e.g. shutdown).
This means that even when only one IO controller fails, the other IO controllers associated
with the shared device no longer control the assigned submodule of the output module.
20
Short designation/module
name in the GSD file
DQ 16x24VDC/0.5A HF
DQ 16x24VDC/0.5A HF QI
DQ 16x24VDC/0.5A HF S
DQ 16x24VDC/0.5A HF S QI
DQ 16x24VDC/0.5A HF
MSO
Digital output module DQ 16x24VDC/0.5A HF (6ES7522-1BH01-0AB0)
Configuration software, e.g., STEP 7 (TIA Por-
tal)
Integrated in the
hardware catalog
STEP 7 (TIA Portal) V12
STEP 7 (TIA Portal)
as of V13 SP1 with
HSP 0143
X
X
X
(PROFINET IO only)
(PROFINET IO only)
X
(PROFINET IO only)
(PROFINET IO only)
X
(PROFINET IO only)
(PROFINET IO only)
Manual, 06/2018, A5E35683409-AC
GSD file in
or higher or STEP 7
V5.5 SP3 or higher
X
X
X
X
X