24
Event Log Messages
The following information concerns messages posted to the Event Log pane in the main user interface.
Consult the server help on filtering and sorting the Event Log detail view. Server help contains many
common messages, so should also be searched. Generally, the type of message (informational, warning)
and troubleshooting information is provided whenever possible.
Block may have addresses out of range. | Block start address =
'<address>', Block size = <count> (bytes).
Error Type:
Warning
Possible Cause:
An attempt has been made to reference a block of memory that contains at least one non-existent location
in the specified device.
Possible Solution:
Verify that the tags assigned to addresses are within the specified range on the device and eliminate any
that reference invalid locations.
Error Mask Definitions
B = Hardware break detected
F = Framing error
E= I/O error
O = Character buffer overrun
R = RX buffer overrun
P = Received byte parity error
T = TX buffer full