Also for Siemens SINAMICS G120P: Operating Instructions Manual (28 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (22 pages), Manual (18 pages), Operating Instructions Manual (18 pages)

Siemens SINAMICS G120P Operating Instructions Manual
Technical specifications
Table 6- 3
Technical data of the dv/dt filter compact plus Voltage Peak Limiter, 380 V ... 480 V 3 AC, Part 2
Article No.
I
thmax
Degree of protection
Power loss
- At 50 Hz
- At 60 Hz
Max. permissible cable
length between dv/dt filter
and motor
dv/dt reactor
Terminals
- 1U1/1V1/1W1
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Voltage Peak Limiter
Terminals
- DCPS/DCNS
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
30
6SL3000-
2DE41-4EA0
A
1405
IP00
kW
1.154
kW
1.197
m
for 2 x M12 bolts
for 2 x M12 bolts
M6 screw
mm
430
mm
385
mm
323
kg
168.8
for M8 bolt
for M8 bolt
for M6 screw
mm
277
mm
360
mm
291
kg
19.2
100 (shielded)
150 (unshielded)
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC