Also for Siemens SINAMICS G120P: Operating Instructions Manual (28 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (22 pages), Manual (18 pages), Operating Instructions Manual (18 pages)

Siemens SINAMICS G120P Operating Instructions Manual
Note
Braking resistor / fire alarm sensor interaction
If a braking resistor is placed underneath a fire alarm sensor then the heat produced may
trigger the fire alarm sensor.
Assignment of Braking Module and Power Module
Table 2- 1
Assignment of Braking Module and Power Module
Power Module
6SL3310-1PE33-0AA0
6SL3310-1PE33-7AA0
6SL3310-1PE34-6AA0
6SL3310-1PE35-8AA0
6SL3310-1PE36-6AA0
6SL3310-1PE37-4AA0
6SL3310-1PE38-4AA0
6SL3310-1PE38-8AA0
6SL3310-1PE41-0AA0
Braking resistors
Operating Instructions, 10/2016, A5E32845373B AD
Rated power of
Suitable Braking
the Power
Module
Line voltage 380 – 480 V 3 AC
160 kW
6SL3760-1AE32-6AA0
200 kW
6SL3760-1AE32-6AA0
250 kW
6SL3760-1AE32-6AA0
315 kW
6SL3760-1AE32-6AA0
355 kW
6SL3760-1AE32-6AA0
400 kW
6SL3760-1AE32-6AA0
450 kW
6SL3760-1AE32-6AA0
500 kW
6SL3760-1AE32-6AA0
560 kW
6SL3760-1AE32-6AA0
Suitable braking
Module
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
6SE7032-5FS87-2DC0
Rated power of the
resistor
braking resistor
General
50 kW
50 kW
50 kW
50 kW
50 kW
50 kW
50 kW
50 kW
50 kW
11