Also for Siemens SINAMICS G120P: Operating Instructions Manual (28 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (22 pages), Manual (18 pages), Operating Instructions Manual (18 pages)

Siemens SINAMICS G120P Operating Instructions Manual

Technical specifications

General technical data
Table 6- 1
General technical data
Product standard
Specific technical data
Table 6- 2
Technical specifications for the braking resistor
Braking resistor
P
power (rated power)
DB
P
power
20
Resistance
Maximum current
Voltage
Max. connectable cross-section
Cable entry
Power connection
Degree of protection
Width x height x depth
Weight, approx.
Braking resistors
Operating Instructions, 10/2016, A5E32845373B AD
EN 61800-5-1
6SE7032-5FS87-2DC0
50 kW
200 kW
3.1 Ω (± 8 %)
275 A
670 to 810 V DC
70 mm²
through M40 cable gland
using M12 bolt-type terminals
IP20
736 x 1321 x 484 mm
109 kg
6
21