Parameter
Parameter text
Note: To change P0595 you first need to set P0010 = 5, and then set P0010 back to 0 afterwards.
p595
Selecting technological units
p596
Reference quantity, technological units
p753
CU analog inputs smoothing time constant
p753[0]
AI0 (T. 3/4)
p753[1]
AI1 (T. 10/11)
p753[2]
AI2 (T. 50/51)
p753[3]
AI3 (T. 52/53)
p756
CU analog inputs type
p756[0]
AI0 (T. 3/4)
p756[1]
AI1 (T. 10/11)
p756[2]
AI2 (T. 50/51)
p756[3]
AI3 (T. 52/53)
Note: Set P1080 to around 20% of maximum motor RPM (P0311) - i.e. above stalling speed.
p1080[0]
Minimum speed
p1120[0]
Ramp-function generator ramp-up time
p1121[0]
Ramp-function generator ramp-down time
p1210
Automatic restart, mode
p2200[0]
BI: Technology controller enable
p2201[0]
CO: Technology controller, fixed value 1
p2253[0]
CI: Technology controller setpoint 1
p2264[0]
CI: Technology controller actual value
p2267
Technology controller upper limit actual value
p2268
Technology controller lower limit actual value
p2280
Technology controller proportional gain
p2285
Technology controller integral time
p2292
CO: Technology controller minimum limiting
p2306
Technology controller fault signal inversion
p2390[0]
Hibernation starting speed
p2391[0]
Hibernation delay time
p2392
Hibernation restart value with technology controller
p2393[0]
Hibernation restart speed relative w/o technology controller
p2398
Hibernation operating mode
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r2260
CO: Technology controller setpoint after ramp-function generator
r2272
CO: Technology controller actual value scaled
r2294
CO: Technology controller output signal
Optional. Use the following parameters to prevent nuisance fault output during Hibernation trip and ramp down. They introduce a 10 second delay before
any fault is output on DO-0.
p730
BI: CU signal source for terminal DO 0
p20158
BI: PDE 0 input pulse I
p20159
PDE 0 pulse delay time in ms
r20160
BO: PDE 0 output Q
p20161
PDE 0 run-time group
p20162
PDE 0 run sequence
Page 41 of 50
Building Technologies
Parameter Value
[4] °C
100
0
0
0
100
[0] Unipolar voltage input (0 V ... +10 V)
[0] Unipolar voltage input (0 V ... +10 V)
[2] Unipolar current input (0 mA ... +20 mA)
[6] Temperature sensor Ni1000
300
30
30
[26] Acknowledging all faults and reclosing for an
ON command
Control_Unit : r722.0
26
Control_Unit : p2201
Control_Unit : r755[3]
100
-10
1.2
25
20
[1] Inversion
50
60
1
100
[1] Hibernation active
26
-0.14
0
Control_Unit : r20160.0
Control_Unit : r52.3
10000
0
[5] Run-time group 5
430
Last Revised: 4/11/2011
Unit
ms
ms
ms
ms
rpm
s
s
°C
°C
°C
s
%
rpm
s
°C
rpm
°C
°C
%