Siemens SINAMICS G120P VSD Getting Started Manual - Page 6

Browse online or download pdf Getting Started Manual for Industrial Equipment Siemens SINAMICS G120P VSD. Siemens SINAMICS G120P VSD 50 pages.

Siemens SINAMICS G120P VSD Getting Started Manual
Temperature range
The country of origin and manufacture
Order number
Hardware version
Serial number

2.3 Website link to G120P Manuals

Included is the G120P website link where you can download all of the latest manuals and information. Also
listed are the document ID numbers to make searching easier (The first two are currently supplied in the
boxes).
http://www.automation.siemens.com/mcms/standard-drives/en/low-voltage-inverter/sinamics-
g120p/Pages/sinamics-g120p.aspx
CU230P-2 HVAC - Getting Started Guide
G120P Power Module - Getting Started Guide
CU230P-2 HVAC - Control Unit Operating Manual
CU230P-2 HVAC - Control Unit Parameter Manual
PM230 IP55 - Power Module Hardware Installation
BOP2 Manual
IOP Manual

3 Planning

The G120P was designed to be flexible and adaptable to suit the needs of the HVAC environment. There are
a number of features that help achieve this and should be considered before installation: -
1. The VSD output characteristic can be changed to suit the load type – including energy optimization
and Sensor-less Vector Control. See next page for more information.
2. The VSD overload specification can be selected (LO/HI) to match the dynamic needs of the load.
For more current (and therefore torque) capability, use the High Overload option – which uses the
next size up in power module. See next point, and next page for more information.
3. The standard operating temperature range can be extended (50C with no derating) to suit the
intended install location by using the HI Overload option.
4. There are a number of Human Machine Interface options: -
a. Blanking plate (usually for use with High Level Interface, or to prevent tampering).
b. Basic Operator Panel - helps on cost critical projects.
c. Intelligent Operator Panel - an intuitive interface option. A very useful tool when combined
with the remote handheld kit for commissioning technicians.
d. Remote control and/or monitoring via the BACnet and Modbus (RS485) protocols that are
included as standard.
5. Can be programmed with: -
a. BOP – from application sheet or a program memory (i.e. cloned).
b. IOP – from Wizards, Menu, or sixteen program memories (i.e. cloned).
c. Laptop via USB cable (supplied with Power Module) and freely downloadable 'Starter'
software from Siemens website.
d. SD Card slot – allows up to 100 programs to be stored and cloned (e.g. project back-up).
6. Optional signals cable shield plate – provides a handy fastening and earth bonding point when
using Nylon type cable glands on the shielded signal & communication cables.
7. Free Function Blocks (including 7 day time-switch, logic blocks, and additional PID loops) allow for
flexibility and new application opportunities.
8. HVAC relevant, built-in features like Hibernation, Essential Services Mode, Multi-zone signal
processing, Auto-reset, Flying restart, V-belt failure detection, to name a few.
Page 6 of 50
Is the operating temperature range of the product.
A5E02792536C AB
A5E02923634A
A5E02430659B AD
A5E02297932B AD
A5E02923635A AB
A5E02778927A AB
A5E00110011A AB
Building Technologies
Last Revised: 4/11/2011