Also for Siemens SINAMICS G130: Operating Instructions Manual (24 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (31 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (38 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (24 pages)

Siemens SINAMICS G130 Operating Instructions Manual
Technical specifications
Detailed technical data
Table 5- 2
Technical specifications of motor reactors 380 V – 480 V 3 AC, part 1
Order number
Suitable for Power Module
Rated current
Power loss
- at 50 Hz
- at 150 Hz
Connections
- to the power module (1U1, 1V1,
1W1)
- Load (1U2, 1V2, 1W2)
- PE
Max. permissible cable length
between motor reactor and motor
Degree of protection
Dimensions
Width
Height
Depth
Weight
Table 5- 3
Technical specifications of motor reactors 380 V – 480 V 3 AC, part 2
Order number
Suitable for Power Module
Rated current
Power loss
- at 50 Hz
- at 150 Hz
Connections
- to the power module (1U1, 1V1,
1W1)
- Load (1U2, 1V2, 1W2)
- PE
Max. permissible cable length
between motor reactor and motor
Degree of protection
Dimensions
Width
Height
Depth
Weight
22
6SL3000-
2BE32-1AA0
6SL3310-
1GE32-1AAx
A
210
kW
0.436
kW
0.486
M10
M10
M8
m
IP00
mm
300
mm
285
mm
257
kg
66
6SL3000-
2BE35-0AA0
6SL3310-
1GE35-0AAx
A
490
kW
0.448
kW
0.5
M12
M12
M8
m
IP00
mm
300
mm
365
mm
277
kg
100
2BE32-6AA0
2BE33-2AA0
1GE32-6AAx
1GE33-1AAx
260
310
0.454
0.422
0.5
0.47
M10
M10
M10
M10
M8
M8
300 (shielded)
450 (unshielded)
IP00
IP00
300
300
315
285
277
257
66
66
2AE36-1AA0
2AE38-4AA0
1GE36-1AAx
1GE37-5AAx
605
840
0.798
0.75
0.9
0.84
M12
M12
M12
M12
M10
M10
300 (shielded)
450 (unshielded)
IP00
IP00
410
410
392
392
292
292
130
140
Operating Instructions, 04/2014, A5E00409660A
2BE33-8AA0
1GE33-8AAx
380
0.447
0.5
M10
M10
M8
IP00
300
285
277
73
2AE38-4AA0
1GE38-4AAx
840
0.834
0.943
M12
M12
M10
IP00
410
392
292
140
Motor reactors