Also for Siemens SINAMICS G130: Operating Instructions Manual (24 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (31 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (38 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (24 pages)

Siemens SINAMICS G130 Operating Instructions Manual
Electrical installation
Cable cross-sections
In a dv/dt filter with separate Voltage Peak Limiter (Type 4), the connections between dv/dt
reactor and Voltage Peak Limiter are already installed on the Voltage Peak Limiter.
Table 4- 1
Table 4- 2
Cable type: 600 V, UL style 3271, operating temperature 125° C
Risk of fire due to ground fault/short-circuit
Inadequate installation of the cables to the Power Module DC link can result in a ground
fault/short-circuit and place persons at risk as a result of the associated smoke and fire.
• Comply with local installation regulations that enable this fault to be ruled out.
• Protect the cables from mechanical damage.
• In addition, apply one of the following measures:
Damage to the dv/dt filter compact due to mechanical load on connections
The connections on the dv/dt filter compact have not been designed for the direct
mechanical connection of the motor cables.
• Take line-side measures to ensure that the connections cannot be deformed by the
32
Cable cross-sections for connections between a dv/dt filter and Power Module
dv/dt filter compact plus Voltage Peak Limiter
Connection cable enclosed for connecting dv/dt reactor and Voltage Peak Limiter
Voltage Peak Limiter
Type 4
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
WARNING
mechanical load exerted by the connected cables.
Type 1
Type 2
Type 3
Type 4
Cross-section
[mm²]
70
Cross-section
[mm²]
Lug for connecting 1U2 / 1V2 / 1W2 on the
dv/dt reactor
M12
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E02590131A
16
25
50
95