Also for Siemens SINAMICS G130: Operating Instructions Manual (24 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (31 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (38 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (24 pages)

Siemens SINAMICS G130 Operating Instructions Manual
Assignment of sine-wave filter and Power Module
Table 2- 1
6SL3310-1GE32-1AA3
6SL3310-1GE32-6AA3
6SL3310-1GE33-1AA3
6SL3310-1GE33-8AA3
6SL3310-1GE35-0AA3
6SL3310-1GF31-8AA3
6SL3310-1GF32-2AA3
Restrictions
The following restrictions must be taken into account when a sine-wave filter is used:
● The output frequency is limited to max. 115 Hz (at 500 – 600 V) and 150 Hz (at 380 – 480
V).
● The modulation type is permanently set to space-vector modulation without
overmodulation.
● The maximum output voltage is limited to approx. 85% of the input voltage.
● Maximum permissible motor cable lengths:
– Unshielded cable: max. 450 m
– Shielded cable: max. 300 m
● During commissioning, the pulse frequency rises to double the factory setting. This
induces current derating, which must be applied to the built-in units' rated currents listed
in the technical specifications.
Note
If a filter cannot be parameterized (p0230 ≠ 3) during commissioning, then no provision is
made for this SIEMENS sine-wave filter for the SINAMICS G130.
Sinusoidal filter
Operating Instructions, 11/2017, A5E00992420A
Assignment of sine-wave filter and Power Module
Power Module
Unit rating of the Power Module
Line voltage 3 AC 380 ... 480 V
110 kW
132 kW
160 kW
200 kW
250 kW
Line voltage 3 AC 500 ... 600 V
110 kW
132 kW
General
Suitable sine-wave filter
6SL3000-2CE32-3AA0
6SL3000-2CE32-3AA0
6SL3000-2CE32-8AA0
6SL3000-2CE33-3AA0
6SL3000-2CE34-1AA0
6SL3000-2CF31-7AA0
6SL3000-2CF31-7AA0