Also for Siemens SINAMICS G130: Operating Instructions Manual (24 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (31 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (30 pages), Operating Instructions Manual (34 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (26 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (42 pages), Operating Instructions Manual (38 pages), Operating Instructions Manual (46 pages), Operating Instructions Manual (28 pages), Operating Instructions Manual (22 pages), Operating Instructions Manual (24 pages)

Siemens SINAMICS G130 Operating Instructions Manual

Electrical installation

Connection
When connecting the motor reactor, you must take into account the following conditions to
ensure that it functions correctly:
● With analog control cables, connecting the shield at both ends can result in coupled-in
noise. To prevent this, the shield must only be connected at one end on the Power
Module.
● Control cables must be routed separately from power cables. Power cables are motor
cables or connecting cables from the DC link of the Power Module (terminals
DCPA/DCNA) to other components (e.g. Braking Module). In particular, you must ensure
that control cables and power cables are not routed in parallel in a joint cable raceway,
even if all the cables are shielded.
● You must use shielded motor cables. The shield for the motor cable must be attached to
the shield plate and motor housing.
● The ground wire for the motor must be fed directly back to the Power Module.
Connection overview
Figure 4-1
Motor reactors
Operating Instructions, 11/2017, A5E00409660A
Connecting the motor reactor and Power Module
4
19