Electrical installation
Connecting the line harmonics filter for SINAMICS G130
Figure 4-5
Thermostatic switch connection
A thermostatic switch is installed to protect the integrated reactors against overload. Its
floating contacts must be integrated in the fault chain on the line side.
Table 4-2
Max. connectable cross-section: 6 mm² (AWG 8)
Rewiring when the line frequency is changed from 50 Hz to 60 Hz
When the line harmonics filter is connected to a network with a line frequency of 60 Hz, the
cable jumpers must be removed in accordance with the instructions in the device (see the
interface overviews).
24
L
1
L
2
L
3
N
PE
M
3 ~
Connecting the line harmonics filter for SINAMICS G130
Thermostatic switch connection
Terminal
T1
T2
Description of function
Thermostatic switch connection
Thermostatic switch connection
Operating Instructions, 07/07, A5E01347987A
Line harmonics filters