Operating Instructions SIPLUS CMS4000 IFN VIB-A
5.1.4
UIK (Unique Identification Key)
The UIK is a clear, device dedicated identification/address. It is printed on the UIK label
plate and deposited in the firmware of the IFN VIB-A. The device is addressed with the
UIK.
In order to communicate with the IFN VIB-A, the UIK must be dedicated during the pa-
rameterization in X-Tools (see manual „SIPLUS CMS4000 X-Tools reference manual").
5.2
Diagnosis via LED-Indicator
Name
Description
Color
Condition
off
blinks
Name
Description
Color
Condition
off
on
Name
Description
Color
Condition
off
on
blinks
Name
Description
Color
Condition
off
on
blinks
SIPLUS CMS4000 IFN VIB-A
Operating Instructions, 11/2014, A5E02297871A-AA
PWR
power Indicator
green
no operation voltage
firmware operates
ERR
error Indicator
red
no error
error
LNK
indicator for connection to the controller
yellow
no connection to the controller
connection to the controller established
data exchange with the controller
CH1-6
error indicator for sensor input CH1-CH6
red
channel is not over parameterization on or no error
sensor cable short circuit
sensor cable break
Siemens Parts