Also for Siemens Sivacon S8: Operating Instructions Manual (7 pages), Operating Instructions Manual (24 pages), Manual (11 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (19 pages), Operating Instructions Manual (12 pages), Operating Instructions Manual (29 pages), Operating Instructions Manual (13 pages), Operating Instructions Manual (24 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (9 pages), Operating Instructions Manual (15 pages), Manual (11 pages), Operating Instructions Manual (9 pages), Repair Documentation (44 pages), Instructions Manual (12 pages), Operating Instructions Manual (11 pages), Operating Instructions Manual (18 pages)

Siemens Sivacon S8 Operating Instructions Manual
Unión atornillada con arandela Belleville /
Tamaño de
Bolting with conical spring washer
rosca /
Par de apriete [Nm] / torque [Nm]
Thread size
Apretar / tightening
M8
M10
M12
Observaciones:
sin mantenimiento/
Remarks:
Tornillo:
clase de resistencia 8,8 (según ISO 898)
Tuerca:
clase de resistencia 8 (según ISO 898)
8 Conexión aislada del cliente (opcional)
El tejido protector no ha sido concebido como protección contra
electrocución, pero sí para evitar defectos por arco eléctrico
Pieza 1 / Piece 1
8PQ9207-7AA03 (350 x 250 mm)
Tejido protector / Protective fabric
Bridas de cables / Cable ties
Agujero para bridas de cables adicionales / Hole for additional cable tie
8PQ9800-7AA72
20
40
70
Maintenance-free
8PQ9207-7AA04 (250 x 250 mm)
Unión atornillada con arandela de seguridad + arandela EN ISO 7089 /
Bolting locking edge washer + washer EN ISO 7089
Par de apriete [Nm] / torque [Nm]
Apretar / tightening
20
40
70
Cuidado necesario, ver también el apartado 2 del instructivo 8PQ9800-7AA73
Maintenance necessary, see also: operating instruction 8PQ9800-7AA73 under
Section 2
Par de comprobación = 85% del par de apriete
Torque check value = 85 % of tightening torque
Screw: Property class 8.8 (acc. ISO 898)
Nut:
Property class 8 (acc. ISO 898)

8 Insulated customer connection (optional)

The protective fabric is not designed to give shock-hazard protection,
but to prevent arching faults.
Pieza 2 / Piece 2
Comprobar / Checking
16
32
60
Pieza 3 / Piece 3
8PQ9138-8AA54 (150 x 250 mm)
7