Siemens SSC161.35U Quick Start Manual - Page 2

Browse online or download pdf Quick Start Manual for Controller Siemens SSC161.35U. Siemens SSC161.35U 17 pages. Electromotoric actuator

Siemens SSC161.35U Quick Start Manual
Use
For 2-way and 3-way Powermite 599 MT Series, 599-02000 - 599-02079
Typical application in chilled ceiling, VAV, unit ventilators, fan coil unit and other terminal
unit applications
Max.10 units of SSC161.05DU, SSC161S.35DU are able to operate in parallel, provided
the controller output suffices.
For 3-position actuator, SSC131.39U, 24 actuators can run in parallel.
SSC131.39U floating fail-safe actuators cannot be run in parallel with legacy SSC81.5U
actuators.
For parallel operation of floating fail-safe SSC actuators all actuators in parallel must be
the same part number.

Technical design

When the actuator is driven by DC 0...10 V positioning signal, it produces a stroke, which is
transmitted to the valve stem.
3-position control signal (for SSC131.39U only)
Voltage at Y1:
Voltage at Y2:
No voltage at Y1 or Y2:
Voltage applied to both Y1
and Y2 (not recommended):
When no power is supplied, the
SSC131.39U actuator fails with
the stem fully retracted.
2
Siemens
Smart Infrastructure
NOTICE
Stem extends
Stem retracts
Actuator maintains its current position
Stem moves to Y2
Normally open valve
closes, normally closed
valve opens
Normally open valve
opens, normally closed
valve closes
A6V12681517_enUS_a