Siemens VALVEGYR LDU11.523A17 User Manual - Page 9
Browse online or download pdf User Manual for Control Unit Siemens VALVEGYR LDU11.523A17. Siemens VALVEGYR LDU11.523A17 22 pages. Valve proving system for automatic shutoff valves ldu11...

Calculation of the leakage rate escaping from a length of pipe
Legend
Example
Building Technologies Division
(P
- P
) x V x 3600
G
W
Q
=
Leck
P
x t
atm
Test
Q
in dm³/h
Permissible leakage rate in dm³ per hour or liters per hour
leck
P
in mbar
Overpressure in pipe section between the valves to be tested, at
G
the beginning of the test phase
P
in mbar
Overpressure set on pressure switch «DW» (normally set to 50
W
% of the gas mains pressure)
P
in mbar
Absolute pressure (1.013 mbar normal pressure)
atm
V
in dm³
Volume of test space confined by the valves to be tested, includ-
ing the space in the valves themselves
T
in s
Duration of proving time
test
P
= 30 mbar
G
P
= 15 mbar
W
P
= 1013 mbar
atm
V
= 10.36 dm³
t
= 27.5 s
Test
Note!
Select volume of pipe section (V) between the gas valves to be checked and over-
pressure (P
set on pressure switch (DW) such that the maximum permissible gas
W)
leakage rate (Q
) will not exceed the rate specified in the local regulations.
Leck
(30 - 15) x 10.36 x 3600
Q
=
Leck
1013 x 27.5
Any valve leakage rate exceeding 20 l/h causes the LDU11...
to initiate lockout
= 20 l/h
CC1N7696en
9/21
20.04.2016