Siemens XC10 Series Operation - Page 14

Browse online or download pdf Operation for Control Unit Siemens XC10 Series. Siemens XC10 Series 32 pages. Extinguishing control unit

Siemens XC10 Series Operation
Extinguishing system overview
3.1

Extinguishing process

14
Building Technologies
Fire Safety
The automatic activation of extinguishing can be blocked as a precaution for
maintenance work. In this instance, in the event of fire, it is possible to press the
Manual Release Button for activation of extinguishing.
Mechanical blocking
For the safety of the people, the extinguishing can be blocked mechanically by
actuating the mechanical blocking device.
The following diagram describes the sequence of an extinguishing process under
normal conditions, i.e. without blocking device actuation and with factory settings.
Fig. 2
Extinguishing process sequence
An automatic extinguishing is enabled after the control unit has run through two
alarm levels - "Fire alarm" and "Activated".
If a detector detects a fire in the extinguishing area (zone 1 or 2), it triggers a "Fire
alarm". The alarm horn sounds slow pulsating and it can be silenced and the
system reset. The fire detectors from zone 3 monitor as a rule the areas adjacent
to the extinguishing area. Zone 3 can also be unused.
If yet another detector of the detector zones detects a fire outbreak in the
extinguishing area (one detector from each of zones 1 and 2) or if the manual
release button is activated (zone 4), the control unit goes over to the "Activated"
state. The alarm horn changes from slow to a pulsating tone. During this time, it is
not possible to silence / re-sound the sounders and all people must evacuate the
area to be flooded. The pre-warning time can be set to between 5 to 60 seconds.
After expiry of the pre-warning time, the releasing element (actuator) is triggered
and the flooding time begins. At the same time the illuminated warning panel is
activated, and the alarm horn changes from pulsating to a continuous sound. After
several seconds, the pressure switch at the cylinder bank reports the release of
extinguishing agent. From this point on, the alarm sounder(s) can be silenced. The
A6V10257477_c_en_--