Cleaning
Replacing spare parts
Accessory/spare part
Operating instructions, German
Electronic controller 110 V-240 V DC/AC
Shunt release Y1
DC 24 V
DC 30 V
DC 48 V
DC 60 V
DC 110 V
DC 125 V
DC 220 V
DC 250 V
AC 100 V
AC 110 V
AC 115 V
AC 120 V
AC 230 V
AC 240 V
9229 0098 176 0-
2019-01-09
1.25 mm.
-
If the value is above the limit - turn the adjusting nut (42) counter-clockwise
at least one turn, approx. 1.5 mm higher.
Use the open-end spanner to prevent the adjusting nut (42) from turning and
securely tighten the locking nut (41).
Function check of mechanical parameters such as on-time and off-time, see
"Rated data of solenoid actuator", Fig 12.
After successful adjustment - install the vacuum contactor in the switchgear.
The insulating parts must be clean if their insulation capacity is to be guaranteed.
Rub insulating parts with a moist cloth.
As a cleaning agent, use only warm water with a mild, liquid household detergent
added and leave to dry.

Accessories and spare parts

To ensure that the device operates reliably, spare parts must be replaced only by
trained and certified personnel.
CAUTION
Risk of injury!
Put the vacuum contactor in the OPEN position. Operate the manual unlatching
if available.
Separate the vacuum contactor from the control feed voltage/switch it off and re-
lease the low-voltage connector/terminal connection.
Remove the vacuum contactor from the system or switch cabinet for maintenance
work.
Order number
9229 0098 100
3TY5902-0AA1
3TY5903-0AB0
3TY5903-0AC0
3TY5903-0AD0
3TY5903-0AE0
3TY5903-0AF0
3TY5903-0AG0
3TY5903-0AH0
3TY5903-0AJ0
3TY5903-0AL0
3TY5903-0AM0
3TY5903-0AN0
3TY5903-0AP0
3TY5903-0AQ0
3TY5903-0AR0
Maintenance