4.2

Mounting instructions

Note
Ideally, mount the device so that the face of the transducer is at least 250 mm (9.84 inch)
above the highest anticipated level.
The device is available in three thread types: 2" NPT, 2" BSPT, or 2" G.
Before inserting the device into its mounting connection, ensure that the threads are of the
same type to avoid damaging them. Simply screw the device into the process connection,
and hand tighten.
4.3
Instructions specific to hazardous area installations (Reference
European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number SIRA
00ATEX1205:
1. The equipment may be used with flammable gases and vapours with apparatus group IIC
and temperature class T5.
2. The equipment is certified for use in an ambient temperature range of -20 to +60 °C
(-4 to +140 °F).
3. The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
4. Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and
EN 60079-17 in Europe).
5. Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
6. Components to be incorporated into or used as replacements in the equipment shall be
fitted by suitably trained personnel in accordance with the manufacturer's documentation.
10
Operating Instructions, 01/2019, A5E32268616-AB
Pointek ULS200