Siemens SITRANS L Series Operating Instructions Manual - Page 33
Browse online or download pdf Operating Instructions Manual for Switch Siemens SITRANS L Series. Siemens SITRANS L Series 50 pages. Capacitance transmitters
Also for Siemens SITRANS L Series: Compact Operating Instructions (45 pages), Operating Instructions Manual (33 pages), Operating Instructions Manual (44 pages)
Service and maintenance
5.1
Maintenance notes
Opening the lid (cover)
Before opening the lid for maintenance reasons observe following items:
- Do not remove the lid while circuits are alive.
- No dust deposits or whirlings are present.
- No rain can enter into the housing.
Frequent check of the unit
To ensure durable safety in hazardous locations and with electrical safety, following items
must be checked frequently depending on the application:
- Mechanical damage or corrosion of any components (housing side and sensor side) and
of the field wiring cables.
- Tight sealing of the process connection, cable glands and enclosure lid.
- Properly connected external PE cable (if present).
Note
Cleaning
If cleaning is required by the application, following must be observed:
- Cleaning agent must comply with the materials of the unit (chemical resistance). Mainly the
lid sealing, cable gland and the surface of the unit must be considered.
The cleaning process must be done in a way, that:
- The cleaning agent cannot enter into the unit through the lid sealing or cable gland.
- No mechanical damage of the lid sealing, cable gland or other parts can happen.
A possible accumulation of dust on the unit does not increase the maximum surface
temperature and must therefore not be removed for purposes of maintaining the surface
temperature in hazardous locations.
SITRANS LVS300
Operating Instructions, 05/2019, A5E44908583-AB
CAUTION
CAUTION
5
33