Siemens SKB60 Manual - Page 20

Browse online or download pdf Manual for Switch Siemens SKB60. Siemens SKB60 32 pages. Auxiliary switch
Also for Siemens SKB60: Mounting Instructions (6 pages), Mounting Instructions (10 pages), Mounting Instructions (7 pages), Mounting Instructions (6 pages), Mounting Instructions (10 pages), Mounting Instructions (4 pages)

Siemens SKB60 Manual
Signal inputs / signal outputs
Override control Z SK6..
Position feedback U SK6..
Enhanced functions SKB60
Selection of direction of operation
Stroke limit control
Sequence control
Signal addition
Communication SKB62/MO
Communication protocol
20
Siemens
Smart Infrastructure
Resistor
Z not connected, priority terminal Y
Z connected directly to G
Z connected directly to G0
Z connected to M via 0...1000 Ω
DC 0...9.8 V
Load impedance
DC 4...19.6 mA
2),
SKB62UA
SKB60,
Direct-acting / reverse-
SKB62UA
acting
SKB62UA
Range of lower limit
Range of upper limit
SKB62UA
Terminal Y
Starting point of sequence 0...15 V adjustable
Operating range of
sequence
SKB62UA
Z connected to R of
Frost protection monitor
Frost protection monitor
Modbus RTU
Number of nodes
Adress range
Factory setting
Transmission formats
Factory setting
Baud rates (kBaud)
Factory setting
Bus termination
Factory setting
0...1000 Ω
No function
Max. stroke 100 %
Min. stroke 0 %
Stroke proportional to R
> 10 kΩ
< 500 Ω
DC 0...10 V / DC 10...0 V
DC 4...20 mA / DC 20...4 mA
0...1000 Ω / 1000...0 Ω
0...45 % adjustable
100...55% adjustable
3...15 V adjustable
0...1000 Ω, added to Y signal
QAF21..
DC 1.6 V, added to Y signal
QAF61..
RS-485, not galvanically isolated
Max. 32
1...248 / 255
255
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
1-8-E-1
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Auto
120 Ω electronically switchable
Off
CM1N4564en
2023-10-17