Cisco 2821 Series Quick Start Manual - Page 24

Browse online or download pdf Quick Start Manual for Network Router Cisco 2821 Series. Cisco 2821 Series 47 pages. 2800 series integrated services routers
Also for Cisco 2821 Series: Installation And Upgrades (21 pages), Datasheet (20 pages), Operations (31 pages), Operations (31 pages)

Cisco 2821 Series Quick Start Manual
Approved Scenarios and Scenarios Not Approved for Dual DC Power Supply Configuration
You can connect a single DC power source to either the A input or the B input. If there are dual power sources, connect one
source to the A input and one source to the B input. Both sources must be the same polarity (with respect to ground) and voltage
(within 0.25 volts). Do not connect –DC grounded and +DC grounded dual sources to Cisco 2811, Cisco 2821, and
Cisco 2851 series integrated services routers.
Dual sources with opposite-polarity grounding damage equipment.
Caution
In Figure 21, either the positive source terminal or the negative source terminal is tied to ground.
Figure 21
Connecting to One Source Only—Source A or Source B
A-
+
A+
B+
B-
In Figure 22, source A and source B share common negative terminal connections.
Figure 22
Connecting Source A and Source B with Common Negative Terminals
Va
+
+
Vb
In Figure 23, source A and source B share common positive terminal connections. This is allowed only if Va equals Vb (within
0.25 V).
When connecting source A and source B with common positive terminals, if source A and source B voltages are
Caution
unequal by more than 0.25 V, the higher-voltage source can discharge into the lower-voltage source through the A-
and B- input terminals. Excessive discharging currents through these terminals can cause one or both of the dual
input DC power supply's internal A- or B- fuses to open, resulting in lack of redundancy or system failure. When
source A and source B are within 0.25 V, discharge current is minimal.
24
+
A-
A+
B+
B-
A-
A+
B+
B-