C2AI MVE2 65 Series Manual - Page 5

Browse online or download pdf Manual for Controller C2AI MVE2 65 Series. C2AI MVE2 65 Series 7 pages. Globe valves actuators

C2AI MVE2 65 Series Manual
DIP SWITCHES SETTINGS
Set the DIP switches according to tables below. Power down and
power up again the actuator or act on the manual override handle
to be sure that settings will be recognized.
Factory settings
DIP
switch
U= feedback
1
Modulating Control (MOD) (Input between Y [+] and M [-])
2
3
Modulating Control 0-10Vdc
4
Sequence Control 0-5Vdc with DIP n. 4 OFF only
5
Sequence Control 2-6Vdc with DIP n. 4 ON only
6
(input between Y [+] and M [-])
Automatic Calibration: the actuator updates the stroke range
7
if an unexpected mechanical stop is detected for at least 10s
OFF
Direct Action
-
(DIP n. 2 OFF only)
(DIP n. 3 ON only)
Voltage Input Signal Vdc
U= feedback
U = 2V
U = 10V
3 point floating (INC) ( Y1 open-extend , Y2 close-retract
Selection of sequence mode, control range defined by DIP n.
Modulating Control 2-10Vdc
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
Current Input Signal 4-20mA (input between Y [+] and M [-]).
In this case DIP n. 4 must be set to ON.
Manual Calibration: the actuator calibration is started moving
the DIP from OFF to ON or vice versa. With DIP in ON in case
of extra stroke or if an unexpected endpoint is detected, the
actuator will never update the stroke
ON
Reverse Action
connected to M)
Y1
Y2
5
(DIP n. 2 OFF only)
(DIP n. 3 ON only)
U=10V
U = 2V
Page 5