C2AI MVE210-65 Manual - Page 6

Browse online or download pdf Manual for Controller C2AI MVE210-65. C2AI MVE210-65 7 pages. Globe valves actuators

C2AI MVE210-65 Manual
DIAGNOSTIC - ALARM FUNCTIONS
LEDs
Error
behaviour
Valve stroke
1
RED ON
less than
5mm
RED LED
quick
Stroke
2
blinking
longer than
+ GREE
60mm
ON
Unexpected
stall
RED Quick
3
within the
Blinking
calibrated
stroke range
Stroke
RED Quick
4
longer than
Blinking
expected
RED slow
Low Power
5
Blinking
Voltage
RED slow
High Power
6
Blinking
Voltage
Actuator use
Automatic calibration
(DIP N. 7 OFF)
The actuator
pushes/pulls 2 times
(unexpected stall) trying
to remove the possible
obstacle. After 2 tries an
Calibration/
alarm is signalled and
first installation
the actuator moves to
initial position and does
not respond to control
signal. Stroke value is
not updated because
out of range
The actuator exits the
60mm stroke range
and it moves toward
the new stroke limit
signalling an anomaly.
The actuator pushes/
pulls 2 times against the
Calibration/
new stroke limit, then it
first installation
goes back to the initial
position still signalling
the anomaly until it is
not within 60mm. The
actuator does not
calibrate the stroke
after 10s (wrong range)
The actuator tries 5
times against the new
normal
stall condition and then
operation
after 10s the actuator
updates the new stroke
length
The actuator moves
toward the new stall
Normal
condition with a lower
operation
speed; after 10s the
actuator updates the
new stroke value
The actuator is
Normal
still working but
operation
performance cannot
be guaranteed
The actuator is
Normal
still working but
operation
performance cannot
be guaranteed
Actuator behaviour
Manual calibration
(DIP N. 7 ON)
The actuator pushes/
pulls 2 times against
endpoint during
calibration and the
actuator moves to the
initial position and then
it does not respond to
the control signal. The
actuator keeps the
previous stroke
The actuator exits the
60mm stroke range
and it moves toward
the new stroke limit
signalling an anomaly.
The actuator pushes/
pulls 2 times against the
new stroke limit, then it
goes back to the initial
position still signalling
the anomaly until it is
not within 60mm. The
actuator does not
calibrate the stroke
after 10s (wrong range)
The actuator tries 5
times against the new
stall condition. At the
end of the attempts the
fault will be signalled.
The actuator does not
update the new stroke
length, but after 60s
makes other attempts
to verify the stall
condition
The actuator moves
toward the new stall
condition with a lower
speed; after 10s the
actuator does not
update the new stroke
value
The actuator is
still working but
performance cannot
be guaranteed
The actuator is
still working but
performance cannot
be guaranteed
Typical trouble
Reset
shooting condition
procedure
Remove
Valve with a stroke
power and
length lower than
power up
5mm
again
Remove
Valve with a stroke
power and
length longer than
power up
60mm
again
Inverted
Valve stuck
control
signal
Stem connection
Inverted
loose or valve
control
damaged
signal
1. . Wrong transform
size
Correct
Voltage
Power
2. . Unstable pow
1. . Wrong transform
Correct
size
Voltage
Power
2. . Unstable pow
Page 6