ASSEMBLING
The actuator can be mounted with any orientation but never up-side
down. When the fluid temperature exceed 120°C the actuator shall
be mounted leaning 45°.
T fluid MAX 120°C
T fluid ≥ 120°C
To mount the actuator on to a valve, position the valve stem to the
bottom of its travel, slide the actuator onto the valve neck, adjusting
with the manual override the screw jack position so the square nut
on the valve spindle fits into the groove on the cross bar. Then slide
the brace into the groove on the valve neck and secure the nuts.
See mounting instructions for full details (MVE2xx_DIM205).
MAINTENANCE
The actuator is maintenance free.
ACCESSORIES
DMVE
End point auxiliary switches
248
Yoke heater 24V, 50W (suggested when the fluid temper-
ature is below 0°C) *
GMVE
Thermal insulation for MVE actuators *
GMVE.S
Thermal insulation for MVE.S actuators *
89404-05 PG13.5 cable gland for cables with Ø variable between 6
and 12 mm
* It is not possible to install both thermal insulation (Gxxxx) and stem
heaters.
Current C2AI valves
(except for 2TGB.F/3TGB.F PN16)
VSXT09PBP, VSXT10PBP ***
2TGB.F/3TGB.F PN16
C2AI valves with threaded M40
connections
T fluid ≥ 120°C
(except for VSB/VMB/VSBF/VMBF
PN16)
VSB/VMB/ VSBF/VMBF PN16
Other manufacturers
Landis *
Danfoss (VR/VF (S) models)
TAC DN15-V298
TAC DN15-V2XX/V3XX
Honeywell**
Airtek
Johnson Controls code VB7816-2111
Johnson Controls code BM-3018-
3300
Tac Venta
(/) this model can not be assembled
(*) AG70-10 for valves having stem Ø 10mm
AG70-14 for valves having stem Ø 14mm
(**) valid for the following models
M6: V176A. B, V538C
1/4": V5011A
(***) assembled only with MVE204S-65 actuator
ELECTRIC CONNECTIONS
Remove the cover screw with a screwdriver and then remove the
cover as shown in the picture beside.
MVE2xx-65 is equipped with a 6 poles removable terminal block for
actuator control and with a not removable 2 poles terminal (F and
N) for main control; the each pole of the plug is clearly marked and
the same label are reported on the electronic board. Before pow-
ering up the actuator make sure the plug is properly connected to
the electronic board and the label on the plugs and on the board
match.
Use cable gland IP65 PG13,5 model.
LINKAGE
MVE2xx-65
(not required)
AG51
AG52
AG70-10
AG70-14
AG60-07
AG 60-08
AG 60-09
AG 60-10
AG 60-11/
AG60-12
AG 66
AG 67
(not required)
MVE2xxS-65
/
/
(not required)
/
(not required)
/
AG63
/
/
/
/
/
/
/
/
/