2.6 Installation of the Water Damper

All units must be equipped with a motorized valve because of the following main reasons.
(1) There would be a water flood risk for some units without motorized valves in the event that they stop
under the cooling conditions.
(2) Under the cooling and heating conditions, energy loss would happen to the chilled water and hot water.
Notes:
(a) The pipe must be wrapped by heat insulation material to prevent condensing water drips.
(b) It is prohibited to bind directly the water valve wire and sponge up with the copper tube, as there would
be probably a short circuit or even electric leakage. The right way is letting the water valve wire go
through the pipe sleeve and then binding the sponge and pipe sleeve.
(c) It is prohibited to put the valve core upside down.

2.7 Electric Wiring

2.7.1 Safety Precautions for Electric Appliances
(1) A dedicated power supply circuit should be used in accordance with local electrical safety regulations.
(2) Don't drag the power cord with excessive force.
(3) The unit should be reliably earthed and connected to an exclusive earth device by the professionals.
(4) The air switch must have the functions of magnetic tripping and heat tripping to prevent short circuit
and overload.
(5) The minimum distance between the unit and combustive surface is 1.5m.
(6) The appliance shall be installed in accordance with national wiring regulations.
(7) An all-pole disconnection switch with a contact separation of at least 3mm in all poles should be
connected in fixed wiring.
Make sure the live wire, neutral wire and earth wire in the family power socket are properly connected.
There should be reliable circuit in the diagram.
Inadequate or incorrect electrical connections may cause electric shock or fire.
2.7.2 Earthing Requirements
(1) The FCU is type Ⅰ electric appliance. Please ensure that the unit is reliably earthed.
(2) The yellow-green wire in air conditioner is the earthing wire which can not be used for other purposes.
Improper earthing may cause electric shock.
(3) The earth resistance should accord to the national criterion.
Nut
Spring washer
Washer
O-ring
Connection nut
Nut
O-ring
Washer
Spring washer
FCU pipe
Be sure there is an
interval of 6-7mm when
the fitting is completed.
Before installed the two pipes must be
tightened with the steps of the connection nut.
Be sure there is an
interval of 6-7mm when
the fitting is completed.
Connection pipe
Fig. 10
NOTE
Fan Coil Unit Wall Mounted Type