DIGITEN DTC-101 Manual - Page 7

Browse online or download pdf Manual for Thermostat DIGITEN DTC-101. DIGITEN DTC-101 10 pages.

DIGITEN DTC-101 Manual

Function Introduction

1.Cooling Mode

Set RV(RUN temperature) > SV(STOP temperature), the temperature
controller enter cooling mode. The LCD will display
When PV(measuring temperature) is higher than RV, the cooling
equipment starts working, and run LED will be turned on. When PV(measuring
temperature) reaches to SV(STOP temperature), the cooling equipment stop
working, and stop LED will be turned on.
Note: When run LED is flashing, it means the cooling equipment enter
compressor delay protection function.

2.Heating Mode

Set RV(RUN temperature) < SV(STOP temperature), the temperature
controller enter cooling mode. The LCD will display
When PV(measuring temperature) is lower than RV, the heating
equipment starts working, and run LED will be turned on. When PV(measuring
temperature) reaches to SV(STOP temperature), the heating equipment stop
working, and stop LED will be turned on.
3.High/Low Temperature Alarm (AH/AL)
When measuring temperature (PV) ≥ high temperature alarm value (AH),
high temperature alarm will be triggered, buzzer will alarm with tone "bi-bi-Biii"
, press any key to cancel the alarm sound, if user want to close alarm, please
reset the AH value or wait until the PV is lower than AH.
When measuring temperature (PV) ≤ low temperature alarm value (AL),
low temperature alarm will be triggered, buzzer will alarm with tone "bi-bi-Biii"
, press any key to cancel the alarm sound, if user want to close alarm, please
reset the AL value or wait until the PV is more than AL.
4.Time of Compressor Delay Starting (DP)
Under refrigeration mode, after power on, if the measuring temperature (PV)
is higher or equal to Run Temperature (RV), the cooling equipment won't start
refrigeration immediately, but it will wait for a delay time(DP) to work.
When the time interval between two refrigeration operations is larger than
-5-
,
,