IV. Signal Lost
In case the RF and WIFI signal lost/disconnected, LED 2 will flicker slowly.
Open Window Detection
When the Open Window detect function is enabled in the parameter setting, the system will automatically stop heating
when it detects a sudden drop of room temperature (2°C in 15 minutes as default). This is normally caused when a
window or door is opened without turning off the heating device.
The device will return to the previous mode of operation after 30mins, then OP disappear. Press any button will exit OWD
function during the heating off period.
Parameter Setting
Under off mode, press and hold SET button and + button for 6s to enter parameter setting. Each press of SET button will
go to next item setting. Adjust the value by pressing + or – button.
Menu
Description
01
Temp. calibration for internal sensor
02
Set Point Max.
03
Set Point Min.
05
Frost Protection Temp.
09
Dead zone
10
Display
12
Open window detect function
13
OWD Detect Time
14
OWD Drop temp. select
(within detect time)
15
OWD Delay time select
(Return to previous working status)
17
Factory reset
18
Software version
Wiring Diagram
Wireless Room Thermostat Optima W R2 +
Range
-8 ℃ ~8 ℃
5 ℃ ~35℃
5 ℃ ~35℃
5 ℃ ~15℃
0~3℃
0: Room temp.
1: SET temp.
1: Enable 0: Disable
2~30mins
2.3.4'C
10~60min
0: No
1: Yes, and then press
On/off button for 5s,wait
until thermostat restart
7109
Default Value
0℃
35 ℃
5 ℃
5 ℃
0℃
0
0
15mins
2 'C
30mins
0