Toshiba 13342 Installation Manual - Page 15

Browse online or download pdf Installation Manual for Air Conditioner Toshiba 13342. Toshiba 13342 18 pages.

Toshiba 13342 Installation Manual
Outdoor Unit
10

Pump-down Operation

Pump-down Operation (Recovering refrigerant)
CAUTION
Since the forcible running for collecting
refrigerant stops automatically after
10 minutes, fi nish collecting refrigerant
within 10 minutes.
Electric current is applied on the
control board. Beware of electric
shock.
• The following must be certainly done
during pump down.
• Do not incorporate air into the
refrigeration cycle.
• Close the service valves. Stop
the compressor and remove the
refrigerant pipe.
If the refrigerant pipe is removed
when the compressor is operating
and service valves are opened, the
refrigerant cycle will inhale unwanted
matter such as air and the pressure
in the cycle becomes abnormally
elevated. It may cause a burst or injury.
1. Remove the valve cover screws.
2. Pull the valve cover in the direction of arrow, and remove it.
D800
3. Turn on the circuit breaker to supply electricity.
In the initial LED display status, D805 is lighted as below.
: ON,
™
D800
D801
D802
˜
˜
˜
Start running all the indoor units connected to the outdoor unit in the
cooling mode.
The checking procedure cannot be completed if the cooling mode is not
operated in every indoor units.
Valve cover
LED
Service switches
D801
D803
D805
SW02
D802
D804
SW01
: OFF,
: Rapid Flashing (5 times/sec.),
˜
: Slow Flashing (1 time/sec.)
¯
D803
D804
˜
˜
4. Hold down SW01 for at least 5 seconds, and check that D800 is lighted
and D804 light is fl ashing (1 time/sec.).
D800
D801
™
5. Press SW01 for 1 time. Then D804 light is fl ashing (5 times/sec.).
D800
D801
™
6. Press SW02 for 1 time. Then D805 light is fl ashing (5 times/sec.).
D800
D801
™
7. Hold down SW02 for at least 5 seconds. Then outdoor unit start cooling
mode.
(The display is kept during the refrigerants collection operation.)
D800
D801
™
8. Close the valve stem of the service valve at the liquid end.
9. Make sure that the compound pressure gauge reading is –101 kPa (–76
cmHg)
10. Close the valve stem of the service valve at the gas end.
11. The refrigerants collection operation is fi nished in maximum 10 minutes.
After the collection is fi nished, promptly stop the operation of all the
indoor unit.
(There are cases that the compressor restarts.)
12. When you want to start over the operation of the SW01 and SW02, press
the SW01 and SW02 at the same time for 5 sec. (It back to the initial
condition of 3.)
However, do not execute the operation during the refrigerants collection.
If by any chance the collection is stopped by the operation, start over the
refrigerants collection operation.
11

Troubleshooting

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C.
board of the outdoor unit in addition to using the check codes displayed on
the remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check
codes displayed on the remote controller of the indoor unit are described in
the Installation Manual of the indoor unit.
LED displays and check codes
Display
D800
D801
D802
D803
(YL)
(YL)
(YL)
(YL)
˜
˜
˜
™
*
˜
˜
˜
™
*
˜
™
*
™
*
˜
˜
˜
™
*
™
*
˜
™
*
˜
™
*
™
*
™
*
™
*
™
*
˜
˜
˜
™
*
˜
˜
˜
™
˜
*
™
*
™
*
˜
˜
˜
™
*
™
*
˜
™
*
˜
™
*
™
*
™
*
™
*
™
*
˜
˜
˜
™
*
˜
˜
˜
™
*
˜
D805
™
*
˜
™
*
™
˜
™
*
™
*
˜
˜
˜
™
*
˜
˜
˜
™
*
˜
™
*
˜
™
*
14
Installation Manual
D802
D803
˜
˜
˜
D802
D803
˜
˜
˜
D802
D803
˜
˜
˜
D802
D803
˜
˜
˜
: ON (
* : 3 sec ON/0.5 sec OFF),
™
™
Indoor
check
D804
D805
code
(YL)
(GN)
Normal operation (no error)
˜
˜
-
˜
˜
1C
Compressor case thermostat error
21
High pressure switch error
˜
˜
1C
Compressor system error
˜
˜
˜
˜
1D
Compressor lock
1F
Compressor breakdown
˜
˜
˜
˜
14
Driving element short circuit
16
Position detection circuit error
˜
˜
™
*
˜
17
Current detection circuit error
1C
Communication error between MCU
™
*
˜
™
˜
1A
Fan system error
*
™
*
˜
1E
Discharge temperature error
Discharge temperature sensor
™
*
˜
19
(TD) error
Outdoor air temperature sensor
™
*
˜
1B
™
(TO) error
Suction temperature sensor (TS)
™
*
˜
18
error
Heat exchanger temperature
™
*
˜
18
sensor (TE) error
Gas pipe (unit A) temperature
˜
™
*
1C
sensor (TGa) error
Gas pipe (unit B) temperature
1C
˜
™
*
sensor (TGb) error
Gas pipe (unit C) temperature
1C
˜
™
*
sensor (TGc) error
˜
™
*
-
PMV error (SH≥20)
-
PMV error (SH≤–8)
˜
™
*
™
*
™
*
20
PMV leakage error (unit A)
20
PMV leakage error (unit B)
™
*
™
*
™
*
™
*
20
PMV leakage error (unit C)
-
Miswiring (mispiping) check error
™
*
™
*
D804
D805
¯
˜
D804
D805
˜
D804
D805
D804
D805
¯
™
EN
FR
: OFF
˜
Description
DE
IT
ES
PT
GR
PL
CZ