Dimplex Westcott 12kW Stove User Manual - Page 6
Browse online or download pdf User Manual for Stove Dimplex Westcott 12kW Stove. Dimplex Westcott 12kW Stove 12 pages. Westcott 12kw stove
Also for Dimplex Westcott 12kW Stove: User Manual (13 pages)
Any remedial work to the chimney flue should be carried out by a
suitably Qualified Engineer. A flue draught of minimum 12 Pascal
is required for satisfactory appliance performance.
An extractor fan must not be used in the same room as this
appliance.
Installation Clearances
The stove can be recessed in a suitable sized fireplace but a
permanent free air gap of at least 150mm must be left around the
sides and 300mm around the top to obtain maximum heat output
and for access to the rear of the stove (Fig 6).
Table 4 shows the minimum safe distances to combustable
materials that must be observed. Any surrounding combustible
material should not exceed 80°C.
Table 4
Sides
Westcott 5kW
600mm
Westcott 8kW
600mm
Floor Protection
In all instances the stove should be positioned on a non-
combustible hearth. The construction of the hearth must conform
to Building Regulations, must be firm, non-combustible and capable
of supporting the stove.
Care should be taken to ensure the stove is level and the hearth
is secure. The hearth itself should not be less than 125mm thick,
including the thickness of the floor and any decorative top surface
(e.g. tiling). Allow an apron of at least 300mm at the front of the
stove in case of spills when de-ashing (Fig 6).
Place the product in the desired location on fireproof hearth taking
note of installation clearances (Fig 7). Adjust the screws on the
bottom of the feet to ensure the stove is level and steady (see 'A'
Fig 2). The stove can be screw fixed to the floor when placed in
the desired position, using the holes provided in the feet.
Flue Pipes
The flue pipe used to connect to the stove should be made of
cast iron, 316 grade stainless steel or vitreous enamelled steel,
nominal thickness 1.2mm. The diameter of the flue pipe should
be 125mm (5") for the Westcott 5kW and 150mm (6") for both the
Westcott 8kW & 12kW models.
Connect the flue pipe to the stove making sure that it fits snugly
into the base of the flue collar (Fig 5). Seal the collar and flue
connection with fire cement or with other suitable high temperature
sealant. Add flue sections as required; note that all flue sockets
must face upwards. Ensure that the flue pipe end is no closer
than 76mm to the side or rear of the chimney walls. It is essential
that all connections between the stove and the chimney flue are
sealed and made airtight.
Avoid using bends greater than 45° to the vertical (Fig 8). All flue
pipes should be as close to vertical where possible. For rear flue
connection the length of the horizontal run of the flue pipe should
not exceed 150mm (Fig 9).
Both chimney and flue pipe must be accessible for cleaning and
if ALL parts of the chimney cannot be reached, a soot door must
be fitted to enable this to be done.
This product should not be installed on a shared flue.
- 2 -
Existing Fireplace
An existing fireplace opening can be bricked up or sealed with a
register plate, 2.5mm sheet steel or concrete. A short length of
flue pipe may then be used to connect the stove to the chimney.
Ideally the old fireplace should be filled in so that there is a smooth
streamlined entry into the flueway. (Fig 9)
Typical installation for Inglenook Fireplaces
Inglenook fireplaces can have very large bore chimneys (Fig 10).
Check with your installer – you may need a stainless steel flexible
flue liner for solid fuel fitting.
Flue Damper (Not Supplied)
When burning wood, a flue damper may be fitted to reduce the
draught through the stove if the draught is too high. When the
damper is set in the open position the chimney draws at full
draught, increasing the volume of air flow through the stove and
Rear
flue. Shutting the damper restricts the flow, slowing the rate of
400mm
burning.
480mm
The damper should be fitted to the stove flue and should be the
same size as the flue pipe. As a rule it should be fitted no closer
than 700mm from the flue outlet of the appliance.
A flue damper should not be fitted when burning solid fuels
other than wood.
Flue Deposits
If the chimney was previously used as an open fire, it is possible
that the higher flue gas temperatures generated by the stove may
loosen deposits that were adhering to the inner surface of the flue
pipe and may cause blockage of the flue pipe. We recommend that
in such a situation a second sweeping of the chimney should be
carried out within one month of initial stove use after installation.
Also lock or close off any existing dampers in the flueway.
Commissioning
Upon completion of installation, the stove and flue system should
be tested by a suitably qualified person to make sure it is safe for
normal use. A smoke draw test should be completed to check for
soundness of joints and seals and also that all smoke and fumes
are taken from the appliance up the chimney and emitted safely.
First warm the flue with a blowlamp or similar for about 10 minutes.
Place a lit smoke pellet on the centre of the grate with the air
controls open. Close the door – the smoke should be drawn up the
flue and be seen to exit from the flue terminal. Complete the test
with all windows and doors shut in the room where the appliance
is fitted. If a ceiling fan is present it must be operated on max for
the duration of the test. If there are any extraction fans in adjacent
rooms these too must be operated on maximum setting during the
test with the interconnecting doors open. If any spillage occurs,
recheck the suitability of the flue system making sure there is
adequate air supply to the room (as per Building Regulations).
Light the appliance and slowly increase the temperature to
operating levels. Open the main fire door when the appliance
reaches normal operating condition and carry out a spillage test
using a smoke match or pellet around the door opening. If any
spillage occurs, open all windows, allow the fire to go out and
recheck the flue system and ventilation.
UK