Ariston ACO 32 MFFI Installation And Servicing Instructions - Page 9

Browse online or download pdf Installation And Servicing Instructions for Boiler Ariston ACO 32 MFFI. Ariston ACO 32 MFFI 49 pages. Aco series

27/32 RFFI SYSTEM
2.5. M
A
OUNTING THE
Fasten the boiler in place using the template and anchors
supplied with the unit. It is highly recommended that a spirit level
be used to position the boiler so that it is perfectly level.
For additional information, please consult the instructions
contained in the connection kit and the flue kit.
For safety purposes, have a competent person carefully check
the electrical system in the property, as the manufacturer will not
be held liable for damage caused by the failure to earth the
appliance properly or by anomalies in the supply of power. Make
sure that the residential electrical system is adequate for the
maximum power absorbed by the unit, which is indicated on the
rating plate. In addition, check that the section of cabling is
appropriate for the power absorbed by the boiler.
F
PPLIANCE
2.6. E
LECTRICAL
The boiler operates with alternating current, as indicated in the
technical data table
power is also indicated. Make sure that the connections for the
neutral and live wires correspond to the indications in the
diagram. The appliance electrical connections are situated on
the reverse of the control panel (see the Servicing Instructions
for further information
I
!
MPORTANT
In the event that the power supply cable must be changed,
replace it with one with the same specifications. Make the
connections to the terminal board located within the control
panel, as follows:
- The yellow-green wire should be connected to the terminal
marked with the earth symbol; make sure to re-use the ferrule
mounted on the other supply cable;
- The blue wire should be connected to the terminal marked "N";
- The brown wire should be connected to the terminal marked "L".
F
. 2.3
IG
. 2.2
IG
Note: The diagrams for the electrical system are indicated in
section 2.11.
Warning, this appliance must be earthed.
External wiring to the appliance must be carried out by a
competent person and be in accordance with the current I.E.E.
Regulations and applicable local regulations.
The appliance is supplied with a fly-lead already connected, this
must be connected to a 240v supply fused at 3A and must
facilitate complete electrical isolation of the appliance, by the
use of a fused double pole isolator having a contact separation
of at least 3 mm in all poles or alternatively, by means of a 3 A
fused three pin plug and unswitched shuttered socket outlet
both complying with BS 1363.
The point of connection to the Electricity supply must be readily
accessible and adjacent to the appliance unless the appliance is
installed in a bathroom when this must be sited outside the
bathroom (see section 2.2).
Should external controls be required, the design of the external
electrical circuits should be undertaken by a competent person,
see Section 2.10 for further information.
2.7.
G
AS
The local gas region contractor connects the gas meter to the
service pipe.
If the gas supply for the boiler serves other appliances ensure
that an adequate supply is available both to the boiler and the
other appliances when they are in use at the same time.
Pipe work must be of an adequate size. Pipes of a smaller size
than the boiler inlet connection should not be used.
C
ONNECTION
(Section 1.2),
where the maximum absorbed
Section
6).
85 mm
220 mm
C
ONNECTION
9