Ariston GENUS PREMIUM EVO HP 150 Design, Installation And Servicing Instructions - Page 18

Browse online or download pdf Design, Installation And Servicing Instructions for Boiler Ariston GENUS PREMIUM EVO HP 150. Ariston GENUS PREMIUM EVO HP 150 44 pages. Wall-hung condensing gas boiler hp
Also for Ariston GENUS PREMIUM EVO HP 150: User Manual (17 pages), User Manual (24 pages)

Ariston GENUS PREMIUM EVO HP 150 Design, Installation And Servicing Instructions
installation

Table of fl ue gas exhaust duct lengths

Type
45
MIN
C13
C33
1
Coaxial
C43
system
B33
1
C13
S1 = S2
C23
C33
0,5 / 0,5
C43
Twin-pipe
1 + S2
C53
System
C83
1
B23
0,5
Type
85
MIN
C13
C33
1
Coaxial
C43
system
B33
1
C13
S1 = S2
C23
C33
0,5 / 0,5
C43
Twin-pipe
1 + S2
C53
System
C83
1
B23
0,5
Type
115
MIN
C13
C33
Coaxial
C43
system
B33
C13
S1 = S2
C23
C33
0,5 / 0,5
C43
Twin-pipe
1 + S2
C53
System
C83
1
B23
0,5
S1 = air suction S2 = Flue gas exhaust
18
Maximum extension
exhaust-air (m)
65
MAX
MIN
MAX
12
1
8
12
1
8
S1 = S2
24/24
0,5 / 0,5
15/15
1 + S2
49
1
16
49
0,5
30
Maximum extension
exhaust-air (m)
100
MAX
MIN
MAX
5
1
5
5
1
5
S1 = S2
24/24
0,5 / 0,5
24/24
1 + S2
49
1
49
49
0,5
49
Maximum extension
exhaust-air (m)
150
MAX
MIN
MAX
S1 = S2
21/21
0,5 / 0,5
14/14
1 + S2
44
1
27
43
0,5
28

Type of air suction/fl ue gas exhaust ducting

Combustion air drawn from the room
Diameter
B23
External fl ue gas exhaust
of pipe
Air drawn from the room
(mm)
ø 80/125
B33
Individual or shared fl ue
ø 80/125
gas exhaust ducting built
into the building
Air drawn from the room
ø 80/80
ø 80/80
Combustion air intake from outside
ø 80
C13
Flue gas exhaust and
air suction duct through
external wall in the same
range of pressure
Diameter
of pipe
(mm)
C33
Flue gas exhaust
andair suction duct
from outsidewithroof
ø 110/150
terminalin the same range
of pressure
ø 110/150
ø 100/110
C43
Individual
fl ue gas exhaust and
ø 100/110
air suction through fl ue
ducting built into the
building
ø 110
Diameter
of pipe
(mm)
C53
Flue gas exhaust leading
outside and air suction
ø 110/150
duct through external wall
not in the same range of
pressure
ø 110/150
ø 100/110
C83
Flue gas exhaust through
ø 100/110
individual or shared fl ue
ducting built into the
building
ø 110
Air
external wall
or
shared
suction
through