Ariston GENUS PREMIUM EVO HP 150 Design, Installation And Servicing Instructions - Page 33

Browse online or download pdf Design, Installation And Servicing Instructions for Boiler Ariston GENUS PREMIUM EVO HP 150. Ariston GENUS PREMIUM EVO HP 150 44 pages. Wall-hung condensing gas boiler hp
Also for Ariston GENUS PREMIUM EVO HP 150: User Manual (17 pages), User Manual (24 pages)

Ariston GENUS PREMIUM EVO HP 150 Design, Installation And Servicing Instructions
description
notes
SERVICE CODE
Rotate encoder clockwise to select code 234 and press O
COMPLETE MENU
0 NETWORK
0. 2 BUS NETWORK
0. 2. 0 Network Presence
Indication of the devices connected via BUS.
0. 4 BOILER USER INTERFACE
0. 4. 0 Zone to be set by display
0. 4. 2 Thermoregulation button
deactivation
2 BOILER PARAMETERS
2. 0 GENERAL
2. 0. 0 DHW Setpoint
Temperature
Setting by DHW button 2
2. 2 BOILER GENERAL SETTINGS
2. 2. 0 Soft ignition
2.2.0 Soft ignition
Maximum value
Minimum value
see Table summarising changes
2. 2. 3 Underfl oor thermostat
or zone 2 ambient
thermostat selection
2. 2. 4 Termoregulation
Termoregulation can be activated by pressing the AUTO
button.
2. 2. 5 Heating ignition delay
2. 2. 8 Boiler version
ATTENTION !
Modify from 1 to 2 only
with connection to an
external storage with
thermostat ON/OFF
ONLY FOR SERVICE - To be used only in substitution P.C.B.
2. 2. 9 Set boiler heat power
ONLY FOR SERVICE - To be used only in substitution P.C.B.
value
K
Boiler
from 1 to 3 (nr)
0 = Enabled AUTO
button
1= Disabled AUTO
button
from 40 to 60 (°C)
from 0 to 100
60 %
100%
0%
0 = Floor safety
thermostat
1 = Zone 2 ambient
thermostat
0 = Absent
1 = Present
0 = Deactivated
1 = 10 seconds
2 = 90 seconds
3 = 210 seconds
from 0 to 5
0 = NOT USED
1 = storage with
NTC
2 = storage with
thermostat
3 = NOT USED
4 = NOT USED
5 = NOT USED
description
notes
2. 3 CENTRAL HEATING PARAMETER - PART 1
2. 3. 1 Maximum Central Heating
power Adjustable heating
see Table summarising changes
2. 3. 2 D.H.W. Maximum power
percentage
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 3 Minimum power
1
percentage
0
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 4 C. Heating Maximum
power percentage
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 5 Anti-cycling time mode
2. 3. 6 Anti-cycling time
(If 235 = 0)
2. 3. 7 Central Heating pump
overrun
2. 3. 8 Pump speed control
GENUS PREMIUM EVO HP 45/65/85*/100*
*= with Optional Pump Kit (Two speed)
2. 3. 9 Set Delta T Pump
Parameter to set if Pump Speed control (237) is setted
on modulating
GENUS PREMIUM EVO HP 45/65/85*/100*
0
*= with Optional Pump Kit (Two speed)
ΔT (fl ow - return) for circulation pump modulation
This parameter can be used to set the diff erence
between the fl ow and return temperatures, which
0
determines the commutation between low and
high circulation pump speed. E.g.: param. 14 = 20
if the Tfl ow - Tret > 20°C; the circulation pump will
be activated at maximum speed. If the Tfl ow - Tret
0
< 20 - 2°C; the circulation pump will be activated at
minimum speed.
The minimum wait time between speed changes is 5
minutes.
1
2. 4 CENTRAL HEATING PARAMETER - PART 1
2. 4. 1 Central heating circuit
pressure to signal a fi lling
request
if the pressure falls down to the pre-set alert value, the
boiler will signal a malfunction warning (1P4
insuffi cient circulation; the request for re-establishing the
correct value will appear on the display.
2. 4. 3 Post-ventilation after
Central Heating request
technical area
value
from 0 to 100
from 0 to 100 (%)
from 0 to 100 (%)
from 0 to 100 (%)
0 = Manual
1 = Automatic
from 0 to 7
(minutes)
from 0 to 15 (minutes)
o CO (continuos)
0 = Low speed
1 = High speed
2 = Modulating
from 10 to 30 (°C)
from 4 to 8
(0,x bar)
Warning 1P4
Filling Needed
ALERT
0 = OFF
1 = ON
60
100
100
1
3
3
2
20
6
1P4) for
0
33