Ariston microCombi Servicing Instructions - Page 10
Browse online or download pdf Servicing Instructions for Boiler Ariston microCombi. Ariston microCombi 28 pages. Type c boilers
Also for Ariston microCombi: Installation Instructions Manual (25 pages)
Soft-light
Adjustment
NB.: It may be necessary to reset the flame failure reset
a number of times during this operation.
10. Remove the pipe from the pressure gauge and connect
screw "C" to the pressure test point in order to seal off
the gas.
11. Carefully check the pressure test points for gas leaks
(valve inlet and outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas
connections, always check for leaks using a soap and water
solution.
10
Supplied By www.heating spares.co Tel. 0161 620 6677
Max Heating
Adjustment
1.4.2 Removing the spark generator
1. Disconnect ignition leads "S" by pulling upward
(F
. 1.27);
IG
2. Remove the screw "T" (F
3. Remove the spark generator by pulling forward from the
gas valve (F
. 1.29).
IG
. 1.28);
IG
S
F
. 1.27
IG
T
F
. 1.28
IG
F
. 1.29
IG