ABB COM600 series Product Manual - Page 12
Browse online or download pdf Product Manual for Control Unit ABB COM600 series. ABB COM600 series 20 pages. Automation platform
Station Automation
COM600
Product version: 3.4
Table 6. Inspection of mechanical structure
Description
Markings and mechanical structure According to IEC 60255-5, -6
Degree of protection by enclosure
Clearance and creepage distances
Table 7. Power supply and module tests
Description
Auxiliary voltage
Aux. voltage interruptions
Ripple in auxiliary DC voltage
Power consumption
Table 8. Insulation tests
Description
Dielectric test
Impulse voltage test
Insulation resistance
Protective bonding impedance
Table 9. Electromagnetic compatibility tests
The EMC immunity test level meets the requirements listed below:
Description
1 MHz burst disturbance test
• Common mode
• Differential mode
12
Standard
According to IEC 60529
According to IEC 60255-5
Standard
According to IEC 60255-6
According to IEC 60255-11
According to IEC 60255-11 12%, f = 2 x fn
According to CE EN 61010
Standard
According to IEC 60255-5
2 kV, 50 Hz for 1 minute
According to IEC 60255-5
5 kV, 1.2/50 μs, 0.5 J
According to IEC 60255-5
>100 MΩ, 500 Vdc
According to IEC 60255-27
<0.1 Ω.
1MRS756764 B
Standard
According to IEC 61000-4-18
and IEC 60255-22-1
2.5 kV
1.0 kV
ABB