Commissioning and Test Procedure

10
Commissioning should be performed when the fire control panel is not in an
alarm/fault condition. Note: No personnel should be in the risk area until
the fire system is fully isolated.
To ensure that the FirePro system will operate as designed, it should be
inspected and serviced every 6 months, and yearly, in accordance with
AS1851 and AS5062.
Six Monthly Test Procedure:
• Isolate the control panel and disconnect the any installed FirePro
aerosol generators. This will generate a fault on the fire control panel.
• Connect FP-08800 Test Module(s) to the "Discharge" output to the
panel (marked yellow). Turn off the Isolate function. The Test Module
should remain installed throughout the test procedure.
• Control Panel and components:
-
Clean and remove dirt, grease or foreign material.
damaged or have been painted.
-
Check all indicators are in normal position.
• FirePro Aerosol Generators:
-
Inspect FirePro generators to ensure they are in good condition.
-
Check mounting brackets are in good condition and secure.
-
Check Dust Covers are in good condition – replace as necessary.
-
Check FirePro Units are at predetermined aiming points.
Fire Detection and Activation System
Model 08451
Replace any parts that appear