8. Troubleshooting
OUTPUT UNIT X
→
FAULT
STATUS UNIT X
→
FAULT
9. Specifications
Size
Material
IP Rating
Op. Voltage
Current – Quiesant
Current – Alarm State
Sigma_XT_signs_m3.5.docx
Output Unit refers to a SIGN, this fault will be
•
Address is the same as another device in the 485 circuit
•
Power has failed to the sign.
•
RS485 signal has failed to the sign.
Status Unit refers to an LCS, this fault will be
•
Address is the same as another device in the 485 circuit
•
Power has failed to the LCS.
•
RS485 signal has failed to the LCS.
Internal Sign
195 x 300 x 50mm
1.2mm steel Epoxy c oa t
IP 40
15V to 30V DC
20 mA
140 mA
External Sign
195 x 300 x 50mm
Thermoplastic
IP 55
15V to 30V DC
20 mA
140 mA
Local Control Station
135 x 186 x 50mm
1.2mm steel Epoxy coat
IP 40
21 to 30v DC
60 mA
70 mA