Thermostat Operation

Minimum Run Time (MRT)
The thermostat has a Minimum Run Time after the start of any heating or cooling call. This
minimum run time assures even heating and cooling cycles. The MRT delay will keep the
system on even if reaches setpoint or you change the setpoint to a temperature that would
satisfy the call, until the MRT expires. Changing the Mode to OFF will cancel the MRT and
the system will turn off immediately. The MRT can be adjusted in the Installer Settings
menu of the thermostat.
Note: The MRT status is shown in the thermostat System Status on-screen labels.
Minimum Off Time (MOT)
The thermostat has a Minimum Off Time after any heating or cooling call is finished. This
delay prevents rapid heating/cooling cycles and also provides "short cycle protection" for
compressor calls. This delay may be noticeable when you change a setpoint and it does
not respond immediately due to another call that has recently completed and the MOT
delay timer is preventing the system from restarting. The MOT delay time can be adjusted
in the Installer Settings menu of the thermostat. There is a minimum of 5 minutes delay to
assure compressor protection.
Note: The MOT status is shown in the thermostat System Status on-screen labels.