[7.3] METHOD 3 : AIR VELOCITY GREATER THAN 500 FPM:
First, verify the air speed is greater than 500 feet per minute by using the measurement method described in
method 1 above. With the air handler turned on, use a manometer to measure the differential pressure across the
inlet port and outlet ports of the sampling tube, this measurement shall be verified to be between 0.0028 to 1.49
inches of water. Please ensure that the end of the tube is completely sealed by use of a plug, or a duct tape in
order to obtain proper measurements.
[8] DETECTOR CONDITION INDICATION
Detector condition is indicated by the detector LED, and the corresponding LEDs on the power board. The
power board has four separate LEDs to indicate the status of the detector. Refer to Table 8.1 for more details.
Table 8.1
Status
Description
Standby
Detector in normal
operation
Maintenance
Fixed LED 3: detector is
removed
Flashing LED 3:
detector is contaminated
Alarm
Detector detects smoke
Trouble
Power failure
Linked alarm
AUX relays are in alarm
from other
mode due to smoke
UG-7-A6O
alarm from linked UG-7-
A6O
UG-7-A6O Installation manual
HFE716 Version: 14
Detector
Power board LED
LED: red
number
1
2
Green
Yellow
Off
Off
Status of relays
3
4
Terminals
Yellow
Red
open
9-10
11-12
14-15
7-8
9-10
11-12
14-15
12-13
15-16
Off
Off
7-8
9-10
12-13
15-16
9-10
12-13
15-16
Date: 2014-03-24
Terminals
closed
7-8
12-13
15-16
12-13
15-16
7-8
9-10
11-12
14-15
11-12
14-15
7-8
11-12
14-15
page 9