Firetrace™ Automatic Detection Tubing
The Firetrace™ Automatic Detection tubing is the key part of the system and acts as the
detector to activate the valve.
The correct installation of the tubing is important to achieve optimum performance from the
system.
The tubing should be mechanically protected outside the identified risk area and should
remain accessible to allow future servicing.
As heat rises, the Firetrace™ tubing is most efficient when mounted directly above the risk.
The tubing will activate at approximately 120 Degrees Centigrade and care should be taken to
avoid attaching the tubing where temperatures above this are achieved during normal
operation.
It is recommended that the tube is a minimum of 150mm away from exceptionally hot
surfaces or fitted with additional sleeving to avoid false activation.
Firetrace Detection Tube and Discharge Pipe Work Routing
As the Firetrace™ detection tube is flexible the exact tube route can vary from application to
application. The basis of the system design is to circumnavigate the risk area so that any
potential risks are covered.
(see tube bending radius guide on page 15).
The discharge pipe work should be installed so an unimpeded flow is allowed. Bending of the
discharge tube should be done using pipe benders to avoid kinks. The discharge diffusers
should be located for maximum effectiveness on the fire.