First Setup
The First Setup must be done prior to using the controller. Completing the First Setup is the only way to access the
homepage and enable the automatic mode of the controller.
Mark III+: Manual Rebooting Method
If required, here is the procedure to manually reboot the Mark III+:
1- Turn OFF all disconnecting means to de-energize the Mark III+. The Mark III+'s screen should turn black.
2- Press the stop button or wait until the Mark III+'s LED extinguishes.
3- Wait 10 seconds.
4- Turn ON all disconnecting means.
Pressure Transducer Test
The controller will test the pressure transducer at least once a week if no manual run test or no weekly test has
been conducted. During the test, the pressure reading will drop to zero but the controller will not see it as a starting
request. This pressure drop will be recorded in the "Pump Curve" page and in the logs with the message.
Home
Home (Menu)
Home
The home page displays all controller statuses and important values of the controller. This includes all voltages,
currents, pressures, motor state and status
Navigation bar: Pressing this icon will open a navigation menu on the left side of the screen: