CALEFFI QuickSetter+ 132658AFC User Manual
Hot water recirculation
Balanced example
Balancing made fast, easy, and accurate with QuickSetter+
Hot water recirculation systems are designed to minimize wait time for hot water to arrive when a fixture is opened. Systems left unbalanced or improperly
balanced result in wasted water down the drain, a costly and environmentally unfriendly situation - not to mention the undesired annoyance placed on
building occupants. The QuickSetter+ takes the guess work and labor out of balancing. With the valve's exclusively designed venturi mechanism, the
installer simply pulls the flow indicator by-pass pin, adjusts the flow to the desired flow rate while viewing the built-in sight gauge, and releases the pin.
Easy, accurate balancing in seconds. No instruments or reference graphs are needed.
132 series
Balancing valve with flow meter. Sweat union connections ½", ¾", 1". Press union connection ¾". DZR low-lead brass body (<0.25%
Lead content) certified by ICC-ES file PMG-1360. Stainless steel ball. Chrome-plated brass ball control stem. PTFE ball seal seat. PSU
control stem guide. DZR low-lead brass flow meter body and headwork. Stainless steel flow meter bypass valve stem. Stainless steel flow
meter springs. PSU flow meter float and indicator cover. EPDM seals. Provided with inlet flow check valve. Water and glycol solutions.
Maximum percentage of glycol 50%. Maximum working pressure 150 psi (10 bar). Working temperature range 14 to 230 degrees F
(-10 to 110 degrees C). Flow rate range unit of measurement gallons per minute (gpm). Accuracy ± 10%. Control stem angle of rotation
90°. Provide with optional mixed outlet termperature gauge, 30 to 210 degree F scale, 2 inch diameter.