The EIA RS-485 Specification labels the data wires "A" and "B", but many
manufacturers label their wires "+" and "-". In our experience, the "+" wire should
be connected to the "A" line, and the "-" wire to the "B" line.
When wiring RS-485 , use a shielded twisted pair cable with an internal impedance
Ω
of 100-120
. Examples of recommended cables are CAT 5, Belden RS-485 (9841-
9844) and Alpha Wire (Alpha 6222-6230).
The shield of the cables must be directly connected to ground in one
of the nodes. In the other nodes the connection should be made via a
capacitor, i.e. if the shield of the cable is connected to pin 1 in node
1, all the other nodes must be grounded using pin 2.