Alderlea T5 Installation & Operation Manual - Page 9
Browse online or download pdf Installation & Operation Manual for Indoor Fireplace Alderlea T5. Alderlea T5 20 pages.
Fig #4
The chimney may incorporate an
offset. To do this safely, all sections
of listed connector, offset elbows
and chimney section must be
screwed together by at least three
sheet metal screws per joint. The
chimney must be suitably supported
by the chimney manufacturer's
listed offset support.
* 4" diameter air inlet with rodent screen
* If the crawl space is well ventilated it is not
necessary to extend air inlet to outside
020512-20 ALT5
SPARK ARRESTOR
RAIN CAP
3' (914 mm)
MINIMUM
RADIATION SHIELD
MINIMUM 7' (2100 mm)
CEILING HEIGHT
55 1/4" (1403 mm)
48"
(1219 mm)
9
CHIMNEY
STORM COLLAR
ROOF FLASHING
CHIMNEY SUPPORT
CHIMNEY CONNECTOR
NON-COMBUSTIBLE
FLOOR PROTECTOR
HOODED VENT OR
90º ELBOW TURNED
DOWN