WaterPro
Alarm Panel
Model - VA02A
Operation, Maintenance and Installation Manual
Installation of the WaterPro™ Alarm Panel Continued
(Fig. 11)
6. Connect sensor #1 (normally open - dry contact) (rated 9 VDC,
200mA MINIMUM) to terminals C and 1 on the terminal block of the
alarm panel.
Connect sensor #2 (normally open - dry contact) (rated 9 VDC, 200mA
MINIMUM) to terminals C and 2 on the terminal block of the alarm panel.
See Figure 11 for wiring instructions. The alarm is activated by a closed
switch.
Caution!
- When installing the "signaling switch" refer to its
installation instructions for proper installation.
#1
#2
7. Plug in the power supply into a 120VAC, 50/60 HZ standard wall outlet. The green "Power" light should come on.
5 ft max
(Fig. 12)
8. Test the system by pressing the "Test" pushbutton or by activating
the "signaling device" (Fig. 12). The buzzer should annunciate and the
red LEDs should illuminate. Press the "Silence" switch. The buzzer
OR
should silence but the alarm LEDs should remain "on". Deactivate the
"signalling device" and the alarm LEDs should turn "off". Since the
WaterPro™ Alarm Panel is equipped with "Auto Reset", reactivating
the "signaling device" for a new test cycle will reactivate the buzzer
and alarm LEDs. Test product weekly to ensure system integrity.
Page 4 of 4